г. Санкт-Петербург,
пер. Ульяны Громовой, д. 4
Время работы: Офис: с 9 до 18
Склад: с 8 до 17
8 (812) 385-56-15 Звонок по России бесплатный info@fgrus.ru

BCU 480-10/10/1LW3GBS2/1B1/1 Kromschroder

Артикул
BCU 480-10/10/1LW3GBS2/1B1/1
Дополнительный Артикул
BCU48010101LW3GBS21B11
Бренд
Kromschroder
Описание
Разъем для on-site mounting, для controlling, igniting and monitoring impulse-controlled, modulating or stage-controlled gas burners. Для непрерывного контроля operation with ionization control or UV control using UV sensor UVD. Intermittent operation with UV sensor UVS. Display of the program status, unit parameters and flame signal. Manual operating mode. Diagnosis and adjustment of unit parameters via optical interface using PC software BCSoft. EC-type tested and certified, AGA, FM, EAC and CSA approved, certified для systems up to SIL 3 (compliant with PL e). · Version для pilot and main burners · 1st safety time on start-up (burner/pilot burner) tSA1: 10 s · 2nd safety time on start-up (main burner) tSA2: 10 s · Safety time during operation tSB: 1 s · Air valve control · Mains voltage: 230 V AC, 50/60 Hz · Ignition transдляmer TZI 7,5-12/100 · Front film in English with additional stickers in D, F, I, NL, E · 2 start-up attempts, pilot burner · 1 start-up attempt, main burner · PROFIBUS DP interface · Integrated Variosub PROFIBUS DP chassis socket, 9-pin · 04 Switch-off threshold, burner/pilot burner: 1 micro A · 05 Main burner switch-off threshold: 1 micro A · 12 Restart in the event of pilot burner failure in operation · 13 Fault lock-out in the event of main burner failure in operation · 15 Flame simulation check in start-up position/standby · 16 Permanent pilot burner · 20 Minimum burner on time tB: as safety time on start-up tSA(2) · 21 Minimum burner pause time tBP: 0 s · 23 Burner/pilot burner flame proving period tFS1: 0 s · 25 Main burner flame proving period tFS2: 0 s · 30 Air valve can be activated externally · 31 Air valve cannot be activated externally on start-up · 32 Air valve can be activated in the event of malfunction · 34 Burner on time in Manual mode limited to 5 min. · Pre-wired для double-electrode operation · Minimum time between two start-ups: 30 s Контроллер
Цена
184 558 руб.
Вес
5,10 кг
Теги
Burner control unit, series 400

Узнайте актуальную цену данного товара

Оставьте свой E-mail и наш менеджер ответит вам в течение 15 минут

Доставка от 3 до 10 дней

из Европы Америки и Азии

Гарантия 12 месяцев

на всё оборудование, включая б/у

Можем поставить редкое и снятое

с производства оборудование

Более 5000 брендов

поставим под заказ

Похожие товары

Артикул: IFD 258-3/1W
Бренд: Kromschroder
Описание: Ignites and monitors gas burners, Для непрерывного контроля operation with ionization control, adjustable cut-off point, display для indicating program status and flame signal intensity, IP 54, EU certified, FM and CSA approved · Series 200 · Ionization or UV control · Immediate fault lock-out or restart in the event of flame failure, switchable · Safety time on start-up: 3 s · Safety time during operation: 1 s · Mains voltage: 230 V AC, 50/60 Hz Контроллер
Подробнее
Артикул: BIC 100RGL-250/285-(77)ER
Бренд: Kromschroder
Описание: · Burner size 100 · Cold air · для propane, propane/butane, butane · Torch · Length of steel tube as of furnace flange: 250 mm · Distance from furnace flange to front edge of burner head: 285 mm · Burner head identifier 77 · Construction stage E · для annular excess air burner Разъем Контроллер
Подробнее
Артикул: TJ 0300-A1AMATND2E8XSZ0
Бренд: Kromschroder
Описание: Model: 0300 - 3 000 000 Btu/h (879 kW) · PreheatTemperature: A - No Preheat Ambient · FurnaceTemperature: 1 - Furnace Less Than 1750 Degrees F · FiringPosition: A - Horizontal or Vertical Up · BurnerStyle: M - Medium Velocity Outlet · CombustorType: AT - Alloy Tube · FuelType: N - Natural Gas (CH4) · GasOrifice: D2 - 29.0mm · AirOrifice: E8 - 90.0mm · FlameSupervision: X - 1/2" UV Scanner Adapter Only · NozzleMaterial: S - Standard Nozzle · PipingConnection: Z - Air Welded / Gas NPT · GasOrientation: 0 - Gas Inlet at 0 Degrees with Air Inlet at 0 Degrees Контроллер
Подробнее
Артикул: BCU 460-5/1LW3GBPD3U
Бренд: Kromschroder
Описание: Разъем для on-site mounting, для controlling, igniting and monitoring impulse-controlled, modulating or stage-controlled gas burners. Для непрерывного контроля operation with ionization control or UV control using UV sensor UVD. Intermittent operation with UV sensor UVS. Display of the program status, unit parameters and flame signal. Manual operating mode. Diagnosis and adjustment of unit parameters via optical interface using PC software BCSoft. EC-type tested and certified, AGA, FM, EAC and CSA approved, certified для systems up to SIL 3 (compliant with PL e). · Standard version · Safety time on start-up tSA: 5 s · Safety time during operation tSB: 1 s · Air valve control · Mains voltage: 230 V AC, 50/60 Hz · Ignition transдляmer TZI 7,5-12/100 · Front film in English with additional stickers in D, F, I, NL, E · Integrated industrial chassis plug, 16-pin · High temperature operation: during continuous operation with ionization/UVD · Configured and prepared для UVD 1 · 04 Switch-off threshold, burner/pilot burner: 1 micro A · 12 Fault lock-out in the event of burner failure in operation · 15 Flame simulation check in start-up position/standby · 20 Minimum burner on time tB: as safety time on start-up tSA(2) · 21 Minimum burner pause time tBP: 0 s · 23 Burner/pilot burner flame proving period tFS1: 0 s · 30 Air valve opens with V1 · 31 Air valve cannot be activated externally on start-up · 32 Air valve can be activated in the event of malfunction · 34 Burner on time in Manual mode limited to 5 min. · Pre-wired для double-electrode operation · Minimum time between two start-ups: 15 s Контроллер
Подробнее
Артикул: TJ 0075-A2AMSCNF5D9XSB0
Бренд: Kromschroder
Описание: Model: 0075 - 750 000 Btu/h (220 kW) · PreheatTemperature: A - No Preheat Ambient · FurnaceTemperature: 2 - Furnace 1750 Degrees F to 2500 Degrees F · FiringPosition: A - Horizontal or Vertical Up · BurnerStyle: M - Medium Velocity Outlet · CombustorType: SC - Silicon Carbide · FuelType: N - Natural Gas (CH4) · GasOrifice: F5 - 13.5mm · AirOrifice: D9 - 49.0mm · FlameSupervision: X - 1/2" UV Scanner Adapter Only · NozzleMaterial: S - Standard Nozzle · PipingConnection: B - BSP (Rc) · GasOrientation: 0 - Gas Inlet at 0 Degrees with Air Inlet at 0 Degrees Контроллер
Подробнее
Артикул: BCU 565WC0F3U0D1K1-E
Бренд: Kromschroder
Описание: Разъем для control cabinet installation, для controlling, igniting and monitoring impulse-controlled, modulating or stage-controlled gas burners. Для непрерывного контроля operation with ionization control or UV control using UV sensor UVD. Intermittent operation with UV sensor UVS. Long service life due to replaceable power модуль для fail-safe outputs. Display of the program status, unit parameters and flame signal. Manual operating mode. Diagnosis and adjustment of unit parameters via optical interface using PC software BCSoft. · Version для extended air control · EU certified, certified для systems up to SIL 3 (compliant with PL e) · Mains voltage: 230 V AC, 50/60 Hz · No valve proving system · Air valve control · Flammen?berwachung mit Ionisations- oder UV-Signal · High temperature operation · Screw connection terminals · Individual packaging · Flame control: ionization · 01 Switch-off threshold, burner/pilot burner: 5 micro A · 06 High temperature operation: during intermittent operation with UVS · 07 Burner/pilot burner start-up attempts: 1 · 09 Restart: no · 15 Air deficiency cut-out with fault lock-out · Safety time during operation: 1 s · 34 Pre-purge time tPV: 0 s · 36 Pre-ventilation time tVL: 0 s · 39 Post-ventilation time: 0 s · 40 Capacity control with air valve · 42 Running time: 3 s · 48 Air actuator opens with V1 (1st stage) · 49 Air actuator cannot be activated externally on start-up · 50 Air actuator can be activated in the event of malfunction · 52 Relief valve (VPS): V2 · 61 Minimum burner on time tB: 0 s · 62 Minimum pause time tBP: 0 s · 67 Operating time in Manual mode limited to 5 min. · 68 Function of terminal 50:purge with High signal · 77 User-defined password · 78 Burner application: burner · 94 1st safety time on start-up: 3 s · 95 Flame proving period 1 tFS1: 0 s · 80 Fieldbus communication: with address check Контроллер
Подробнее